Error Display and Troubleshooting
This function displays error location and nature. When a problem
or an error occurs, take the following actions.
Flow display check
Check integrated flow when instantaneous flow is selected
Integrated flow is displayed only during button is pressed.
(Returns to instantaneous flow when releasing
button.)
The unit of integrated flow is changed as[L]→[ m
3
]→
m
3
×10
3
]→[L]if press
button while pressing button.
Check instantaneous flow when integrated flow is selected
Instantaneous flow is displayed only during
button is pressed.
(Returns to integrated flow when releasing
button.)
Switching the unit of integrated flow display
Set the integrated flow display unit while integrated flow is
selected.
1. Unit flickers by pressing
button.
2. The unit is changed as[L]→[ m
3
]→[ m
3
×10
3
]→[L]by
button.
3. Unit stops flickering when deciding the unit by button.
The unit stops flickering unless pressing button for 5 sec.,
and complete switching the flow display unit. Integrated flow
display unit is not switched.
Clear of Integrated Value
Integrated value is cleared by pressing
button pressing
button for 5sec.
SET
Other Functions
Initialize the Set Value
All the setting can be initialized to values at shipment.
Press
button and button for longer than 2 sec. during initial
setting modeF_0. Press button afterF_00appears.
Setting is not initialized but switched toF_0if pressing
button. See below for setting at shipment.
Display setting : Instantaneous flow( d_1)
Unit setting : /min( U_1)
Switch spec. : Instantaneous switch output( oU1_0 )
Output mode : Reverse output( oU1_n )
Flow setting value : Instantaneous flow Intermediate value of
full-range/ Integrated flow 0
Key lock mode : Unlocked( unL)
Flow conversion condition : 20
, 101.3kPa,
65%RH[ANR](Anr)
MODE
SET
To reset display of Error 1 and 3, press
and
button simultaneously.
LED display
Error Nature Troubleshooting
A current exceeding
80mA
is flowing to OUT1.
Turn the power off. Check
the load and wiring of
OUT1.
Set data has been changed
due to some reason.
Reset all the data.
A fluid flow is higher than
rated rate.
Reduce the flow down to
the rated rate.